Roberts Gorden operation & service Service Manual Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
SECTION 1: INTRODUCTION
3 of 40
It will then be possible to set program times and
temperatures for all controls from one location and
copy programs from one control to another.
It will also be possible to read the current status of
all controls from a single station.
1.6 Installation Requirements
1.6.1 Radiant Tube Heaters
The ROBERTS GORDON
®
NRG Control can
operate up to ten burners providing that the
electrical load on each relay does not exceed 7 A
inductive.
Mount ROBERTS GORDON
®
NRG Control (or
remote sensor if fitted) on a wall or column at a
height of approximately 1.5 to 1.8 metres from the
floor.
The ROBERTS GORDON
®
NRG Control, or sensor,
should be in a position to monitor an average radiant
temperature. Keep clear of cold draughts, direct
sunlight, direct radiant field heaters and areas of
little air movement such as corners. For larger
systems, use two remote sensors to provide closer
temperature control.
1.6.2 Warm Air Heaters
The ROBERTS GORDON
®
NRG Control can
operate a single warm air heater. However up to four
heaters may be controlled from each control if each
heater is provided with interface relays See Page 13,
Section 4.7.
Mount ROBERTS GORDON
®
NRG Control, or
remote sensor, on a wall or column at a height of
approximately 1.5 to 1.8 metres from floor. The
ROBERTS GORDON
®
NRG Control, or sensor,
should be positioned where it will monitor an
average room temperature. Keep clear of cold
draughts, direct sunlight, path of warm air from
heater and areas of little air movement such as
corners.
1.6.3 Multiple Unit Considerations
When using control to operate more than one
radiant or warm air heater, careful consideration
should be given to position of control or remote
temperature sensor because single temperature
monitoring point controls all heaters that are
connected. The use of two remote sensors may
provide closer temperature control.
For warm air heaters, the interface relay D 258 must
be installed, in accordance with Page 13, Section
4.7, adjacent to each heater to ensure that the
electrical supply at each heater is isolated for
maintenance.
For larger air heaters, it may not be practical to
operate more than one heater from a single control
due to the larger area covered by these heaters.
Contact Roberts-Gordon Europe Limited for further
advice on control location and application.
1.6.4 Installation Materials
Shielded cable Belden 8451, General Cable C 2514,
or equivalent rated for up to 300 V must be used for
sensors, modulating 0-10 V output, 12 V DC inputs
and network bus connections. Maximum cable
length for each sensor is 100 m. Maximum cable
length for network is 1,000 m. Keep control cables
away from high current mains circuits to prevent
signal interference.
1.6.5 Electrical Requirements
The controller must have a 230 V 50 Hz
power supply wired with the Ferrite EMC filter. See
Page 7, Figure 7 in accordance with relevant wiring
diagram from Page 9, Section 4.
1.7 P ro gramming Details
Every control is programmed with default settings
and may be reconfigured to suit the needs of the
installation. See Page 33, Section 5.6.3 and Page
34, Table 1.
When supplied, each ROBERTS GORDON
®
NRG
Control is configured as a stand alone unit.
Each unit must be configured to operate heating
equipment it is controlling. See Page 33, Section
5.6.3 and Page 34, Table 1.
Programming for stand alone units and network
units is similar. However, for network units, they
must be network configured first. See Page 31,
Section 5.6.1.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Controller must be properly grounded to an
electrical source.
Failure to follow these instructions can
result in death or electrical shock.
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 47 48

Comments to this Manuals

No comments