CRV-SERIES SUBMITTAL SHEET
© 2004 Roberts-Gordon
BEFORE IN STALLATI ON AND OPER ATION OF HEATI NG EQUIPMENT, READ AND U NDERSTAND THE INSTALLATION, OPERATIO N AND SERVICE MANUAL.
APPLICATION S, ENGI NEERING AND DETAI LED GUID ANCE ON SYSTEMS DE SIGN, INSTAL LATION AND PRODUCT PERFORMANCE IS AVAILABLE UPON REQUEST. ROBERT S GORDON
®
PRODUCTS ARE TO BE
INSTALLED ONLY IN ACCORDANCE WITH LOCAL LAWS, CODES AND REGUL ATIONS, AND ONLY BY A CONTRACTOR QUALIFIED I N THE INSTALLATION AND SERVICE OF GAS-FIRED HE ATING EQUI PMENT.
Pump Specifications
* For starter, see National Electric Code (NEC) requirement for motors 1 hp or higher.
Air Supply Blower Specifications
Capacity 240 CFM @ 0.75" w.c.
Power (W) 167
Phase 1
Hertz (Hz) 60
Voltage (V) 120
Full Load Amp (Amps) 1.5
R.P.M. 3000
Motor Enclosure OPEN FC
Inlet/Outlet (In.) 5/5
Weight (lbs.) 10
C
B
G
A
E
D
F
dia.
Pump Specifications
Model EP-100 EP-201 EP-203 EP-301
Horsepower (Hp) 1/3 3/4 3/4 2*
Phase 1 1 3 1
Hertz (Hz) 60 60 60 60
Voltage (V) 115/230 115/230 230 230
Full Load Amp (Amps) 4.8/2.4 6.6/3.3 3.0 11.5
R.P.M. 3450 3450 3450 3450
Motor Frame 56 56 56 90
Motor Enclosure TENV TENV TEFC TEFC
Noise Level @ 5' (DBA) - 70 70 -
Inlet/Outlet (In.) 4/4 4/4 4/4 6/6
Weight (lbs.) 62 112 112 170
Pump Dimensional Data (in.)
Model ABCDEFG
EP-100 17 14.5 21 3.75 10 4 4
EP-201/203 17.75 17 18.75 3.25 10 4.5 4.5
EP-301 25.6 24.8 22.7 4.8 15.2 6 6