WARNINGFOR YOUR SAFETYIf you smell gas:1. Open windows.2. DO NOT try to light any appliance.3. DO NOT use electrical switches.4. DO NOT use any teleph
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL4 Figure 1: Installation Clearances and Clearances to CombustiblesWAR
SECTION 4: SPECIFICATIONS5SECTION 4: SPECIFICATIONS4.1 PGP & POP Internal HeatersDimension Data - PGP & POP Internal HeatersNOTES: Horizontal
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL6 4.2 PGP & POP External HeatersDimension Data - PGP & POP Ex
SECTION 4: SPECIFICATIONS74.3 Air Outlet and Flue Arrangements4.3.1 Vertical and Horizontal Heaters - Free Blowing (top view)NOTE: Models 015-020 are
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL8 4.4 General Technical Data Table (all models)Appliance Category II
SECTION 4: SPECIFICATIONS94.6 Technical Data - Ecoflam Modulating Burners (all models - burner reference "H")NOTE: The air setting is a guid
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL10 4.7 Technical Data - Ecoflam Oil-Fired Burners (burner reference &
SECTION 5: HEATER INSTALLATION11SECTION 5: HEATER INSTALLATION5.1 General Heaters are designed for floor standing vertical installation. Special versi
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL12 Figure 3: Typical Installation of a Oil-Fired Cabinet Heater1 mMin
SECTION 6: FLUE INSTALLATION13SECTION 6: FLUE INSTALLATION6.1 Flue InstallationFlues must be correctly sized for the model. See Page 5, Section 4.1. F
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL14 Figure 6: Guy WireFigure 7: Socket DirectionFigure 8: Flue and Roo
SECTION 7: AIR SUPPLY15SECTION 7: AIR SUPPLY7.1 Air SupplyIt is important to ensure adequate air supply at all times for both combustion and heating r
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL16 SECTION 8: FUEL PIPINGIt is important that the gas supply pipe and
SECTION 8: FUEL PIPING178.2 Fuel Oil Supply8.2.1 Fuel Storage TankThe fuel storage tank should be located outside the building as close as possible to
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL18 Figure 12: Pressurised System Installation - Duplex SystemCheckVal
SECTION 9: WIRING AND ELECTRICAL INFORMATION19SECTION 9: WIRING AND ELECTRICAL INFORMATION9.1 Electrical SupplyA 230 V 50 Hz 1 Ø supply is required fo
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL20 2. The control will then adjust the burner input continuously to a
SECTION 9: WIRING AND ELECTRICAL INFORMATION219.4 CCH Wiring Diagram Oil Models 15-30 (floor standing)Note: Remote fan controlcarries full load of fan
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL22 9.5 CCH Wiring Diagram Gas Models 15-30 (horizontal mounting)Red12
SECTION 9: WIRING AND ELECTRICAL INFORMATION239.6 CCH Wiring Diagram Oil Models 15-30 (horizontal mounting)Red1234N10 AMAIN TERMINALSIN CONTROL PANELB
© 2008 Roberts-Gordon LLCAll rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL24 9.7 CCH Wiring Diagram Gas Models 40-50 (floor standing)Red1234N10
SECTION 9: WIRING AND ELECTRICAL INFORMATION259.8 CCH Wiring Diagram Oil Models 40-50 (floor standing)Red1234N10 AMAINFANMOTORMAIN TERMINALSIN CONTROL
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL26 9.9 CCH Wiring Diagram Gas Models 40-50 (horizontal mounting)Red12
SECTION 9: WIRING AND ELECTRICAL INFORMATION279.10 CCH Wiring Diagram Oil Models 40-50 (horizontal mounting)NOTE:Any of the original wire supplied wit
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL28 9.11 CCH Wiring Diagram Gas Models 60-100 (floor standing)12310 AT
SECTION 9: WIRING AND ELECTRICAL INFORMATION299.12 CCH Wiring Diagram Oil Models 60-100 (floor standing)12310 ATIME/TEMPERATURECONTROLSFAN CONTROLL1FA
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL30 9.13 CCH Wiring Diagram Gas Models 60-100 (horizontal mounting)123
SECTION 9: WIRING AND ELECTRICAL INFORMATION319.14 CCH Wiring Diagram Oil Models 60-100 (horizontal mounting)123410 ABlueFANLIMITFAN / LIMIT STAT7827R
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL32 9.15 Final Connections to Ecoflam HIGH/LOW or Modulating Burners (
SECTION 10: COMMISSIONING33SECTION 10: COMMISSIONINGInstallation, service, commissioning and annual inspection of the heater must be done by a contrac
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL34 Figure 13: Combination Thermostat (all models)10.2 Commissioning t
SECTION 10: COMMISSIONING353. Check gas flow rate at gas meter.10.3 Control - Gas-Fired HeatersFor High/Low and modulating burners, follow the general
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL36 Figure 15: Motor Starter (models 040 -100 and Thermal Overload (mo
SECTION 10: COMMISSIONING37Figure 17: Dungs Gas Valve10.4 Gas ValvesDungs Combination Gas ValveAll model 015 - 030 gas-fired burners operate as direct
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL38 10.5.1 Pressure SwitchSetting of the pressure switch must only be
SECTION 10: COMMISSIONING3910.7.2 Sequence of OperationThe operating sequence is as follows:With the external controls on and calling for heat, the bu
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL40 SECTION 11: USER INSTRUCTIONS11.1 User InstructionsThe COMBAT® Cab
SECTION 11: USER INSTRUCTIONS4111.2.2 Burner Lockout Reset ButtonThe red warning light built into the burner control box will illuminate when the cont
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL42 WARNINGFOR YOUR SAFETYIf you smell gas:1. Open windows.2. DO NOT t
SECTION 12: SERVICING43SECTION 12: SERVICING12.1 Servicing InstructionsAfter commissioning, the heater will require maintenance to be carried out annu
TABLE OF FIGURESFigure 1: Installation Clearances and Clearances to Combustibles ...4Figure
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL44 SECTION 13: CONVERSION BETWEEN FUELS13.1 GeneralAll COMBAT® Cabine
SECTION 14: TROUBLESHOOTING45SECTION 14: TROUBLESHOOTING14.1 GeneralWARNINGExplosion HazardInstallation must be done by a registered installer/contrac
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL46 14.2 Troubleshooting for Oil Burners (see manufacture’s instructio
SECTION 14: TROUBLESHOOTING4714.3 Troubleshooting for Gas Burners (see manufacturer’s instructions)Heater OperatingTROUBLESHOOT ENDS.If problems persi
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL48 14.4 Troubleshooting for Flame Supervision SystemHeater OperatingT
14.5 Troubleshooting for Solenoid Valves Circuit14.6 Troubleshooting for Main Fan Circuit (1 Ø)Fault lies elsewhere.Investigate and correct.Valve faul
14.7 Troubleshooting for Main Fan (3 Ø)Motor running.TROUBLESHOOT ENDS.If problems persist, contactROBERTS GORDON® atTel: +44 (0)121 506 7709www.rg-in
SECTION 15: REMOVAL AND REPLACEMENT PARTS51SECTION 15: REMOVAL AND REPLACEMENT PARTSSee warnings and notes on Page 43, Section 12 before removing or r
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL52 5. Check the correct rotation of the fan as on Page 33, Section 10
SECTION 16: PARTS LIST53SECTION 16: PARTS LISTThe following items are recommended as spares which may be required during routine service and replaceme
WARNING© 2007 Roberts-Gordon, LLC www.rg-inc.com
1 Product ApprovalROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Direc
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL2 SECTION 1: HEATER SAFETYYour Safety Is Important to Us!This symbol
SECTION 3: CRITICAL CONSIDERATIONS3SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationCabinet heaters are supplied with burners suitable for on/of
Comments to this Manuals