WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas suppliers
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clear-
ances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
Installation, Operation
& Service Manual
Models UHA[T][M][X][S]
150, 175, 200, 225
250, 300, 350, 400
UHA-Series
Tubular Unit Heaters
(Standard Range)
P/N 111101NA 11/14 Rev. K
Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
Fax: +1.716.852.0854
Toll Free: 800.828.7450
www.robertsgordon.com
www.rg-inc.com
© 2014 Roberts-Gordon LLC
Combat
®
Page view 0
1 2 3 4 5 6 ... 71 72

Summary of Contents

Page 1 - (Standard Range)

WARNINGFOR YOUR SAFETYIf you smell gas: 1. Open windows. 2. DO NOT try to light any appliance. 3. DO NOT use electrical switches. 4. DO NOT us

Page 2

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL2 of 59Figure 1: UHA[T][M][X][S]150 - 250 Label Placement*For separated combustion u

Page 3 - (Gamme standard)

SECTION 1: HEATER SAFETY 3 of 59Figure 2: UHA[T][M][X][S]300 - 400 Label Placement*For separated combustion units only.**For modulating units only.Des

Page 4

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL4 of 59SECTION 2: INSTALLER RESPONSIBILITYThe installer is responsible for the follo

Page 5 - Roberts-Gordon LLC

SECTION 3: CRITICAL CONSIDERATIONS 5 of 59SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationUHA[T][M][X][S] heaters have automatic ignition burne

Page 6

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL6 of 59SECTION 4: CLEARANCES TO COMBUSTIBLES4.1 Required Clearances to CombustiblesC

Page 7 - TABLE OF FIGURES

SECTION 4: CLEARANCES TO COMBUSTIBLES 7 of 59Figure 3: Installation Clearances and Clearances to Combustibles6"(15 cm)31"**(79 cm)3"(8

Page 8

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL8 of 59SECTION 5: NATIONAL STANDARDS AND APPLICABLE CODES5.1 Gas CodesThe type of ga

Page 9 - SECTION 1: HEATER SAFETY

SECTION 6: HEATER INSTALLATION 9 of 59SECTION 6: HEATER INSTALLATION 6.1 General Heaters are designed for installation above 6' (1.8 m). These h

Page 10 - **For modulating units only

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL10 of 59SECTION 7: VENTING7.1 VentingThis heater must be vented in accordance with t

Page 11

SECTION 7: VENTING 11 of 59concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof. See Page 15, Figure 9 and Page 16, F

Page 13 - RITICAL CONSIDERATIONS

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL12 of 59dampers and any other gas-burning piece(s) of equipment to their previous co

Page 14

SECTION 7: VENTING 13 of 59Figure 6: Standard Vented Heater - Vertical and Horizontal Vent TerminationVentFlashing(By Others)Vent TerminationVerticalO

Page 15 - Installation Clearances

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL14 of 59Figure 7: Standard Vented Heater - Common Vertical Vent TerminationRequirem

Page 16

SECTION 7: VENTING 15 of 59Figure 8: Separated Combustion Heater - Vertical and Horizontal Vent TerminationFigure 9: Concentric Vent BoxModel **Vent D

Page 17 - EATER INSTALLATION

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL16 of 59Figure 10: Concentric Vertical and Horizontal Vent Termination - Separated C

Page 18

SECTION 8: AIR SUPPLY 17 of 59SECTION 8: AIR SUPPLY8.1 Separated Combustion InstallationWhen installed as a separated combustion heater (UHA[T][M][X]S

Page 19 - SECTION 7: VENTING

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL18 of 59SECTION 9: GAS PIPINGA gas meter is connected to the service pipe by the gas

Page 20

SECTION 9: GAS PIPING 19 of 59Figure 11: Gas ConnectionGas Shut-off ValveDrip LegCapUnionConnectionOption B:Medium or HeavyGauge PipeGas ConnectorOpti

Page 21 - 13 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL20 of 59SECTION 10: WIRINGAll heater models require constant 120 V / 1Ø / 60 Hz powe

Page 22

SECTION 10: WIRING 21 of 5910.2 Low Voltage Thermostat for Models UHA[T][M][X][S] 150-400NOTE: Models 300-400 have two axial fans.NOTE: Electrical sup

Page 23 - Figure 9: Concentric Vent Box

AVERTISSEMENTPOUR VOTRE SECURITESi vous sentez une odeur de gaz:1. Ouvrir les fenêtres.2. N’essayer pas d’allumer un appareil.3. N’utiliser pas d’int

Page 24 - 16 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL22 of 5910.3 UHA[X][S] Series Internal Wiring Diagram for Single Stage Gas ValvesNOT

Page 25 - SECTION 8: AIR SUPPLY

SECTION 10: WIRING 23 of 5910.4 UHA[X][S] Series Ladder Wiring Diagram for Single Stage Gas ValvesNOTE:For field wiring into service junction box, or

Page 26

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL24 of 5910.5 UHA[T][X][S] Series Internal Wiring Diagram for Two Stage Gas Valves1W2

Page 27 - SECTION 9: GAS PIPING

SECTION 10: WIRING 25 of 5910.6 UHA[T][X][S] Series Ladder Wiring Diagram for Two Stage Gas ValvesHIGHSTAGENOTE:For field wiring into service junction

Page 28

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL26 of 5910.7 UHA[M][X][S] Series Internal Wiring Diagram for Modulating Gas ValvesNO

Page 29 - SECTION 10: WIRING

SECTION 10: WIRING 27 of 5910.8 UHA[M][X][S] Series Ladder Diagram for Modulating Gas ValvesNOTE:For field wiring into service junction box, or if any

Page 30

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL28 of 5910.9 Electrical Connection to the HeaterNote: Junction box is not provided w

Page 31

SECTION 11: OPERATION AND MAINTENANCE 29 of 59SECTION 11: OPERATION AND MAINTENANCERead this manual carefully before installation, operation, or servi

Page 32

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL30 of 5911.2 Begin Start-Up 11.2.1 Before Operating the HeaterTo ensure that all

Page 33

SECTION 11: OPERATION AND MAINTENANCE 31 of 59Figure 13: Single Stage Gas Valve for Models UHA[X][S] 150 - 400Figure 14: Two Stage Gas Valve for Model

Page 35

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL32 of 59Figure 15: Modulating Gas Valve for Models UHA[M][X][S] 150 - 400Description

Page 36 - 28 of 59

SECTION 11: OPERATION AND MAINTENANCE 33 of 5911.2.2 Start-Up the Gas Valve (All Gases)11.2.2.1 Check Burner Gas Pressure (Single Stage)1. Remove the

Page 37 - PERATION AND MAINTENANCE

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL34 of 5911.3 Pressure SwitchThe pressure switch is factory pre-set for each model an

Page 38

SECTION 12: USER INSTRUCTIONS 35 of 59SECTION 12: USER INSTRUCTIONSThe UHA[T][M][X][S] Series heaters are fully automatic and operate from the externa

Page 39 - 31 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL36 of 59Figure 16: LED Diagnostic CodesLED INDICATION FAULT MODESlow Flash Normal Op

Page 40 - 32 of 59

SECTION 13: SERVICING 37 of 59SECTION 13: SERVICING13.1 Servicing InstructionsAfter start-up, the heater will require maintenance to be carried out, a

Page 41

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL38 of 59and electrical supply. Remove the fan(s) and use a small brush or duster to

Page 42

SECTION 13: SERVICING 39 of 59Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the pipe, gaps in the s

Page 43 - SER INSTRUCTIONS

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL40 of 59Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressur

Page 44 - 36 of 59

SECTION 14: TROUBLESHOOTING 41 of 59SECTION 14: TROUBLESHOOTINGCut/Pinch HazardWear protective gear during installation, operation and service.Edges a

Page 45 - SECTION 13: SERVICING

© 2014 Roberts-Gordon LLCAll rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any

Page 46

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL42 of 5914.1 General

Page 47

SECTION 14: TROUBLESHOOTING 43 of 5914.2 Troubleshooting For Automatic Ignition Burner Systems For your safety and optimum heater performance, use onl

Page 48

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL44 of 5914.3 Troubleshooting for Flame Supervision SystemNOTE: Minimum flame probe c

Page 49 - SECTION 14: TROUBLESHOOTING

SECTION 14: TROUBLESHOOTING 45 of 5914.4 Troubleshooting for Gas Valves14.5 Troubleshooting for Flue Blower Valve faulty.Replace with one of correct t

Page 50 - 14.1 General

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL46 of 59SECTION 15: REPLACEMENT PARTSSee warnings and important information on Page

Page 51

SECTION 15: REPLACEMENT PARTS 47 of 5915.2 Burner Compartment for Models UHA[T][M][X][S] 150-40015.2.1 Burner Compartment without Filler Panel for Mod

Page 52 - 44 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL48 of 5915.2.2 Burner Injectors for Models UHA[T][M][X][S] 150-400MODELUHA[T][M][X][

Page 53

SECTION 15: REPLACEMENT PARTS 49 of 5915.3 Ignition Electrode and Flame Probe for Models UHA[T][M][X][S] 150-400Description Part Number Qty.Spark Elec

Page 54

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL50 of 5915.4 Heat Exchanger The heat exchanger consists of a four-pass design with 1

Page 55 - EPLACEMENT PARTS

SECTION 15: REPLACEMENT PARTS 51 of 5915.6 Flue Blower for Models UHA[T][M][X][S] 150-300 IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED

Page 57

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL52 of 5915.7 Flue Blower for Models UHA[T][M][X][S] 350-400 IT IS IMPORTANT THAT ONL

Page 58

SECTION 15: REPLACEMENT PARTS 53 of 5915.8 Pressure SwitchPull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct

Page 59 - 150 - 300

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL54 of 5915.10.1 Fan Removal and Replacement15.10.2 To Replace the Fan AssemblyTo rep

Page 60 - Rear Panel

SECTION 16: SPECIFICATIONS 55 of 59SECTION 16: SPECIFICATIONS16.1 Dimension Data for Models UHA[T][M][X][S] 150-250Model UHA[T][M][X][S]150 UHA[T][M][

Page 61

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL56 of 5916.2 General Technical Data Table*Do not exceed the maximum length of flue s

Page 62 - Description Part Number Qty

SECTION 16: SPECIFICATIONS 57 of 5916.4 Dimension Data for Models UHA[T][M][X][S] 300-400

Page 63 - SECTION 16: SPECIFICATIONS

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL58 of 5916.5 General Technical Data Table*Do not exceed the maximum length of flue s

Page 64 - 16.3 Technical Data Table

SECTION 17: THE ROBERTS GORDON® UHA-SERIES WARRANTY 59 of 59SECTION 17: THE ROBERTS GORDON® UHA-SERIES WARRANTYROBERTS-GORDON LLC WILL PAY FOR:Within

Page 67 - UHA-SERIES WARRANTY

TABLE OF FIGURESFigure 1: UHA[T][M][X][S]150 - 250 Label Placement ...2Figure 2: UHA[T][M][X][S]300 - 400 Label Placement ...3Fi

Page 72

SECTION 1: HEATER SAFETY 1 of 59SECTION 1: HEATER SAFETYYour Safety is Important to Us! This symbol is used throughout the manual to notify you of po