Installation, Operation
& Service Manual
Models UHD[X][S][R]
75, 100, 125
P/N 113000NA 11/08 Orig.
UHD-Series
Tubular Duct Furnace
(Low Profile Range)
WARNING
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon LLC
1250 William Street
P. O. Box 4 4
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
www.rg-inc.com
© 2008 Roberts-Gordon LLC
Quality in Any Language™
Combat
®
Page view 0
1 2 3 4 5 6 ... 53 54

Summary of Contents

Page 1 - (Low Profile Range)

Installation, Operation& Service ManualModels UHD[X][S][R]75, 100, 125P/N 113000NA 11/08 Orig.UHD-SeriesTubular Duct Furnace(Low Profile Range)WAR

Page 2

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL4 3.6 VentilationIt is important to ensure that there is adequate air space aro

Page 3 - Roberts-Gordon LLC

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES5SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES4.1 Gas CodesThe type of gas appearing on the nam

Page 4

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL6 4.6 High AltitudeThese heaters are CSA-approved (without modifications) for i

Page 5 - TABLE OF FIGURES

SECTION 5: DUCT HEATER INSTALLATION7SECTION 5: DUCT HEATER INSTALLATION 5.1 General To connect the inlet and outlet ducts to the heater, Duct-Mate or

Page 6

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL8 5.2 Shelf Mounting and SuspensionFour suspension points (3/8" nuts) are

Page 7 - SECTION 1: HEATER SAFETY

SECTION 5: DUCT HEATER INSTALLATION9Figure 4: Shelf-Mounting Methods Figure 5: Wall Shelf Mounting and SuspensionShelf Mounting BracketsDescription Pa

Page 8

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL10 SECTION 6: VENTING6.1 Changing Vent and Air Intake OrientationThe heater is

Page 9 - RITICAL CONSIDERATIONS

SECTION 6: VENTING11Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.For vent termination S

Page 10

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL12 and additional sealing measures (high temperature silicone at all seams) are

Page 11

SECTION 6: VENTING13Figure 6: Vent and Roof DetailFigure 7: Standard Vented Heater - Vertical and Horizontal Vent TerminationModel Vent Diameter Part

Page 13 - INLET DUCT

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL14 Figure 8: Standard Vented Heater - Common Vertical Vent Termination

Page 14 - Unistrut

SECTION 6: VENTING15Figure 9: Separated Combustion Heater - Vertical and Horizontal Vent TerminationFigure 10: Concentric Vent BoxModelAir Intake &

Page 15 - UCT HEATER INSTALLATION

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL16 Figure 11: Concentric Vertical and Horizontal Vent Termination - Separated C

Page 16

SECTION 7: AIR SUPPLY17SECTION 7: AIR SUPPLY7.1 Separated Combustion InstallationWhen installed as a separated combustion heater (UHD[X]S[R]), the air

Page 17 - SECTION 6: VENTING

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL18 SECTION 8: GAS PIPINGA gas meter is connected to the service pipe by the gas

Page 18

SECTION 9: WIRING19SECTION 9: WIRINGAll heater models require constant 120 V/1Ø/ 60 Hz power supply. Check heater rating plate for electrical rating

Page 19

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL20 9.3 Internal Wiring DiagramIMPORTANT:For field wiring into service junction

Page 20

SECTION 9: WIRING219.4 Ladder Wiring DiagramIMPORTANT:For field wiring into service junction box, or if any of the original wire supplied with the hea

Page 21

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL22 9.5 Electrical Connection to the HeaterIMPORTANT: Junction box is not provid

Page 22

SECTION 10: OPERATION AND MAINTENANCE23SECTION 10: OPERATION AND MAINTENANCERead this manual carefully before installation, operation, or service of t

Page 23 - SECTION 7: AIR SUPPLY

© 2008 Roberts-Gordon LLCAll rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any

Page 24

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL24 Figure 13: Automatic Burner Control SequenceFigure 14: Gas Valve Burner Sequ

Page 25 - SECTION 9: WIRING

SECTION 10: OPERATION AND MAINTENANCE2510.2.2 Start-Up the Gas Valve (All Gases)10.2.2.1 Check Burner Gas Pressure1. Remove the plug in the outlet (bu

Page 26

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL26 SECTION 11: USER INSTRUCTIONS11.1 User InstructionsThe UHD[X][S][R] Series h

Page 27 - IGNITION

SECTION 11: USER INSTRUCTIONS2711.4.2 To Turn Heater Off Set the thermostat to the "OFF" position.The burner will turn off immediately.To re

Page 28

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL28 SECTION 12: SERVICING12.1 Servicing InstructionsAfter start-up, the heater w

Page 29 - PERATION AND MAINTENANCE

SECTION 12: SERVICING2912.7 Maintenance ChecklistInstallation Code and Annual Inspections: All installations and service of ROBERTS GORDON® equipment

Page 30 - Required Incoming Signals

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL30 Gas Line and Shut-off ValvesCheck for gas leaks.See Page 18, Section 8.Burne

Page 31

SECTION 13: TROUBLESHOOTING31SECTION 13: TROUBLESHOOTING13.1 GeneralEnsure air flow through the heat exchanger is appropriate per the rating plate.If

Page 32 - Reset Button

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL32 13.2 Troubleshooting For Automatic Ignition Burner SystemsIf problems persis

Page 33 - SER INSTRUCTIONS

SECTION 13: TROUBLESHOOTING3313.3 Troubleshooting for Flame Supervision SystemNOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3

Page 35 - SECTION 12: SERVICING

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL34 13.4 Troubleshooting for Gas Valves13.5 Troubleshooting for Flue Blower Valv

Page 36

SECTION 14: REPLACEMENT PARTS35SECTION 14: REPLACEMENT PARTS Burner ComponentsAll serviceable burner parts are accessed by the door on the side of the

Page 37 - 13.1 General

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL36 14.2 Burner Compartment14.2.1 Burner InjectorsRemove flexibleair duct from s

Page 38

SECTION 14: REPLACEMENT PARTS3714.3 Ignition Electrode and Flame Probe14.4 Heat ExchangerThe heat exchanger consists of a six-pass design with 1.5&quo

Page 39

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL38 14.5 Flue Blower Vertical InstallationIT IS IMPORTANT THAT ONLY THE CORRECT

Page 40

SECTION 14: REPLACEMENT PARTS3914.6 Pressure SwitchPull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type o

Page 41 - Flexible Air Duct

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL40 SECTION 15: SPECIFICATIONS15.1 Dimension DataModelUHD[X][S][R] 75UHD[X][S][R

Page 42 - Orifice Marking 49 46 46

SECTION 15: SPECIFICATIONS4115.2 General Technical Data Table*Do not exceed the maximum length of flue stated or heater may not operate properly. 15.3

Page 43 - SECTION 14: REPLACEMENT PARTS

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL42

Page 44

SECTION 16: ROBERTS GORDON® COMBAT® UHD-SERIES WARRANTY43SECTION 16: ROBERTS GORDON® COMBAT® UHD-SERIES WARRANTYROBERTS GORDON® WILL PAY FOR:Within 24

Page 45 - EPLACEMENT PARTS

TABLE OF FIGURESFigure 1: Clearances to Combustibles ... 3Figure 2: Air Flow Direction...

Page 47 - 15.3 Technical Data Table

®OWNER WARRANTY REGISTRATION CARDAbout the Owner:Name:________________________________________________________________________________________________

Page 50

WARNING© 2008 Roberts-Gordon LLC www.rg-inc.com

Page 52

SECTION 1: HEATER SAFETY1SECTION 1: HEATER SAFETYYour Safety is Important to Us!This symbol is used throughout the manual to notify you of possible fi

Page 53

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL2 SECTION 2: INSTALLER RESPONSIBILITYThe installer is responsible for the follo

Page 54

SECTION 3: CRITICAL CONSIDERATIONS3SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationUHD[X][S][R] heaters have automatic ignition burners for ON/